Ontario Building Code · Fire Code · Updated 2026

Are Exit Signs Required to Be Illuminated?

YES — Ontario law requires exit signs to be illuminated at all times, including during power failures.

Ontario Building Code O.Reg 332/12, Article 3.4.5.1 · Ontario Fire Code O.Reg 213/07

Under the Ontario Building Code and Ontario Fire Code, all exit signs in commercial, industrial, and institutional buildings must be continuously illuminated — including during power outages. Here are the exact illumination types, battery backup durations, and inspection rules.

Permitted Illumination Types

The OBC and Fire Code allow four types of illuminated exit signs. All must be certified to the applicable CSA or ULC standard:

1.

Internally Illuminated (LED) — Most Common

Built-in LED or fluorescent light source. Requires battery backup capable of maintaining illumination for a minimum of 2 hours during a power failure. Must be CSA C860 certified.

Standard: CSA C860 · Battery backup: 2 hours minimum · Transfer time: within 10 seconds of power failure
2.

Photoluminescent (Glow-in-the-Dark)

Charged by ambient light — no electrical connection required. Must maintain legible visibility for a minimum of 90 minutes in complete darkness. Requires minimum 25 lux ambient charging light at the sign face.

Standard: ULC S572 · Visibility: 90 minutes in darkness · Charging light: 25 lux minimum at sign face
3.

Edge-Lit Signs

Light source runs along the edge of the sign panel, illuminating the face uniformly. Acceptable when CSA certified with battery backup meeting the 2-hour minimum.

Standard: CSA C860 · Must include battery backup · Battery: 2 hours minimum
4.

Externally Illuminated — Rarely Used for New Installs

A separate light source illuminates the sign face from outside. Acceptable only when connected to emergency power and the sign face meets all visibility requirements. Not recommended for new installations.

Must be connected to emergency power circuit · Not CSA C860 sign type · Unusual in post-2012 buildings
Not Permitted: Non-illuminated exit signs (retroreflective or plain printed signs) do not meet the Ontario Building Code for new or replacement installations. They may be used as supplementary directional signs only — not as the primary exit sign.
CSA C860 / OBC O.Reg 332/12

CSA-Certified Illuminated Exit Signs

From $24.99 CAD — Ships 1-2 business days

Shop Exit Signs

Battery Backup Requirements

Battery backup is the mechanism that keeps your exit signs lit during a power failure. The Ontario Fire Code sets out specific duration, testing, and documentation requirements:

Minimum Duration2 hours of continuous illumination at full brightness on battery power alone
Transfer TimeSign must reach full illumination within 10 seconds of main power failure
Battery TypesSealed lead-acid, NiCd, or NiMH. Must be replaced per manufacturer schedule (typically every 3–5 years)
Monthly Test30-second battery transfer test (manual button or automatic self-test). Results must be logged in the fire safety record
Annual TestFull 2-hour discharge test. Battery must sustain full illumination for the entire 2-hour period
RecordsTest dates, results, and battery replacement dates must be recorded and available for fire inspection
Failed battery = Fire Code violation. A dead or insufficient battery in an internally illuminated exit sign is a compliance failure — even if the sign appears lit during normal power. The annual 2-hour test is the only way to confirm battery adequacy.

Photoluminescent Signs: When They Qualify

Photoluminescent (glow-in-the-dark) exit signs are an acceptable alternative to internally illuminated signs under ULC S572 — but only when specific conditions are met:

Where Photoluminescent Works

  • ✅ Areas with consistent 25+ lux ambient lighting
  • ✅ Stairwells with reliable emergency lighting
  • ✅ Locations where electrical wiring is impractical
  • ✅ Low-level supplementary exit path markings

Where Photoluminescent Fails Code

  • ❌ Spaces where lights are regularly turned off during occupancy
  • ❌ Areas with irregular or dimmed ambient lighting
  • ❌ Locations receiving less than 25 lux at the sign face
  • ❌ Buildings where AHJ (Authority Having Jurisdiction) requires electrical signs

If a photoluminescent sign cannot be verified to receive adequate charging light — for example, in a storage room where lights are routinely off — an internally illuminated LED sign with battery backup is required.

Inspection and Testing Requirements

The Ontario Fire Code requires documented inspections of exit sign illumination systems. Inspectors check these records during routine fire inspections:

Monthly Inspection

  • ✅ Verify all exit signs are illuminated and legible
  • ✅ Press test button — confirm battery transfers within 10 seconds
  • ✅ Check for burned-out LEDs or faded sign faces
  • ✅ Confirm no obstructions blocking sign visibility
  • ✅ Log date and result in fire safety record

Annual Inspection

  • ✅ Full 2-hour battery discharge test — sign must hold full brightness
  • ✅ Battery replacement per manufacturer schedule
  • ✅ Photoluminescent: verify charging lux level at sign face
  • ✅ Check legibility from maximum viewing distance (30 m)
  • ✅ Provide documentation to fire inspector on request

Penalties for Non-Illuminated Exit Signs

Non-illuminated exit sign: Immediate compliance order — 24–72 hours to remedy
Failed battery backup: Fire Code violation — sign treated as non-functional
Missing inspection records: Fine + increased inspection frequency
Repeat non-compliance: Fines up to $50,000 for corporations; $25,000 for individuals
Occupation permit risk: Non-compliant exit signage can result in occupancy restrictions
Source: Fire Protection and Prevention Act, 1997 (S.O. 1997, c.4); Ontario Fire Code O.Reg 213/07

Exit Sign Illumination Compliance Checklist

  • All exit signs are continuously illuminated whenever the building is occupied
  • Signs are CSA C860 (internally illuminated) or ULC S572 (photoluminescent) certified
  • Internally illuminated signs have working battery backup (2-hour minimum capacity)
  • Photoluminescent signs receive minimum 25 lux ambient charging light at the sign face
  • Monthly 30-second battery transfer test completed and logged in fire safety record
  • Annual 2-hour battery duration test completed and documented
  • Batteries replaced per manufacturer schedule (typically every 3–5 years)
  • Signs illuminate within 10 seconds of power failure
  • Sign face is legible from 30 metres under normal lighting conditions
  • No burned-out LEDs, faded faces, or physical damage to sign or lens
  • No obstructions (banners, shelving, merchandise) blocking view of any exit sign

Related Exit Sign & Safety Sign Guides

Order CSA-Certified Illuminated Exit Signs

LED exit signs with battery backup, photoluminescent glow signs, and fire route safety signs. All CSA or ULC certified. Ships in 1–2 business days from Ontario.